FEATURES

 

"MECO-G" AC Reactive (VAR)Transducers convert a sinusoidal AC signal into a standard DC signal which is directly proportional to the measured input signal, These outputs are accurate, reliable, consistent and stable and are suitable for Telemetering, Dataloggers, PLC's, SCADA systems and control applications.

GENERAL SPECIFICATIONS

 

SPECIFICATION
Accuracy ± 0.5% of Rated output, ± 0.2 % (Optional)
Output Ripple 0.2% RMS
Response Less than 0.5 Sec.
Frequency 50 / 60 Hz.
Zero Adj. ± 2% Min
Span Adi. ±10 % Min.
Operating Temp. 0° ~ 50° C (RH < 90 %) Non - Condensing
Storage Temp -20°C ~ 70°C
Overload Continuous 2 x Rated Current, 1.2 x Rated Voltage
Breakdown Impulse Voltage 4.5KV , 1 x 40µs (Without Dewing)
Tempreature Coefficient 0.03% / °C.
Dielectric Withstand Voltage
between Input / Output / Power / Case
2 KV AC for 1 minute.
Insulation Resistance (@ 500V DC) >100MΩ

>
TYPE MODEL INPUT RANGES DIMENSION
SINGLE PHASE

R-RPT 11 -63.5,100, 110,415,440 V (ANY ONE)
0-1,2,2.5,5A (ANY ONE)
Size 2
3 PHASE-3 WIRE R-RPT 33 Size 3
3 PHASE-4 WIRE R-RPT 34Size 3

DC OUTPUT RANGES
0-1V ≥ 1KΩ
0-5V ≥ 5KΩ
1-5V ≥ 5KΩ
0-10V ≥ 10KΩ
2-10V ≥ 10KΩ
0-1mA ≤ 10KΩ
0-5mA ≤ 2KΩ
0-10mA ≤ 1KΩ
4-20mA / 4-12-20mA ≤ 500Ω

AUXILLIARY POWER SUPPLY
0-110 VAC ± 10% 50/60 Hz 2VA Approx.
0-220 VAC ± 10% 50/60 Hz 2VA Approx.
0-24 VDC ± 10% 2Watts Approx.
0-48 VDC ± 10% 2Watts Approx.
0-110 VDC ± 10% 2Watts Approx.
0-220 VDC ± 10% 2Watts Approx.
DIMENSIONS